Code Word |
Description |
Iris |
2 7 STR IRIS BARE AL
|
| AWG
Size |
Stranding |
| 2 |
No.
of Wires |
Class
|
| 7/w |
AA,
A |
| Diameter
(inches) |
| Individual
Wires |
Complete
Cable OD |
| .0974 |
.292 |
Weight
(lbs/1000ft) |
Cross Sectional Area
(sq in) |
Rated
Breaking
Strength (lbs)
|
| 62.3 |
.0521 |
1,350 |
Resistance
(OHMS/1000ft ) |
Current
Rating
(Amps) |
| .260
DC@20°C |
.318
AC@75°C |
185 |
| Standard
Packages |
| Length
(feet) |
Weight
(lbs) |
Reel
Size |
22,470
11,235
3,210 |
1,400
700
200 |
NR
42.28
NR 36.22
Coil |
|
| |
Applications
Stranded 1350 aluminum conductors shown in this section of data are classified
1 as follows: |
| |
Class
AA |
For
bare conductors usually used in overhead lines. |
| |
Class
A |
For
conductors to be covered with weather-resistant materials and for bare conductors
where greater flexibility is required. |
|
Compact strand
conductor for use in bare overhead applications or for use with weather-resistant
coverings or insulations is also available.
Classes refer to stranding and are an indication of relative conductor
flexibility, AA being the least flexible, C the most flexible.
|
Construction
Aluminum alloy 1350-H19 wires, concentrically stranded.
|
|
Specifications
AAC bare conductor meets or exceeds the following ASTM specifications:
|
| B-230 |
Aluminum
Wire, 1350-H19 for Electrical Purposes |
| B-231 |
Aluminum
Conductors, Concentric-Lay-Stranded |
| B-400 |
Compact
Round Concentric-Lay-Stranded, Aluminum 1350 Conductors |
| |
|
1. Resistance
is calculated using ASTM standard increments of stranding and metal conductivity
of 52.5% IACS, AC resistance at 60Hz.
2. Current
ratings are based on 75°C conductor temperature, 25°C ambient, 2ft/s wind,
96/watts/sq. foot sun, .05 coefficients of emissivity and absorption.
|
|
|
|
Electrocables USA
10408 West McNab Road
Fort Lauderdale Fl. 33321
Ph 954.726.1926
Fx 954.726.1928
sales@electrocable.com
cell 954-557-0300 |
|
|