contact us
contact us
about us


336.4 ACSR 26/7 LINNET BARE AL




Code Word
Description
Linnet
336.4 ACSR 26/7 LINNET BARE AL

Conductor

Size (AWG or kemit) Stranding ACSR (Al/Stl)
336.4 MCM 26/7

Diameter (inches)
Individual Wires Steel Core Complete
Cable OD
Alum Steel
.1137 .0884 .2642 .720

Weight (lbs/1000ft) Content %
Alum Steel Total Alum Steel
317.1 145.4 462.5 68.53 31.47

Rated Breaking Strength (lbs) Resistance
(OHMS/1000ft )
Current Rating
(Amps)
14,100 .0505 DC@20C
.0618 AC@75C
529

Standard Packages
Length (feet) Weight (lbs) Reel Size
16,410
8,205
7,590
3,795
RMT 84.36
NR 60.28
 
Applications
Used as bare overhead transmission cable and as primary and secondary distribution cable. ACSR offers optimal strength for line design. Variable steel core stranding enables desired strength to be achieved without sacrificing ampacity.
 
Construction
Aluminum alloy 1350-H-19 wires, concentrically stranded about a steel core. Core wire for ACSR is available with class A, B or C galvanizing; "aluminized" aluminum coated (AZ); or aluminum-clad (AW). Additional corrosion protection is available through the application of grease to the corer or infusion of the complete cable with grease.
 

Specifications
ACSR bare conductor meets or exceeds the following ASTM specifications:

B-230  Aluminum Wire, 1350-H19 for Electrical Purposes
B-231  Aluminum Conductors, Concentric-Lay-Stranded
B-232  Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR)
B-341  Aluminum-Coated Steel Core Wire for aluminum Conductors, Steel Reinforced (ACSR/AZ)
 B-498  Zinc-Coated Steel Core Wire for Aluminum Conductors, Steel Reinforced (ACSR/AZ)
B-500  Zinc Coated and Aluminum Coated Stranded Steel Core for Aluminum Conductors, Steel Reinforced (ACSR)
 

1. Resistance is calculated using ASTM standard increments of stranding, and metal conductivity of 61.2% IACS for EC (1350), and 8% IACS for steel. AC (60Hz) resistance includes current dependent hysteresis loss factor for 1 and 3 layer construction.

2. Current ratings are based on 75C conductor temperature, 25C ambient, 2ft/s wind, 96/watts/sq. foot sun, .05 coefficients of emissivity and absorption.




headquarter

Electrocables USA
10408 West McNab Road
Fort Lauderdale Fl. 33321
Ph 954.726.1926
Fx 954.726.1928
sales@electrocable.com